Name: | FIX-2100 online gas alarm controller |
---|---|
Model: | FIX-2100 |
Control channel: | 4~20mA 1~32 channels |
Alarm function: | LED and buzzer sound |
Alarm output: | 2 way common relay output, 8 programmable relay outputs |
Power supply: | 220VAC |
Name | Online gas alarm controller |
Model | FIX-2100 |
Power supply | 220VAC 50Hz ±5Hz |
Fuse | Rated current: 10A Dimensions: 5mm*20mm |
Max current | 1.5A (24VDC) |
Backup power | 14.8VDC,5.2AH (Lithium polymer battery) |
Output | 24VDC,1000mA |
Working method | Inspection |
Signal input | ① 3-wire 4~20mA ② RS485 MODBUS is optional |
Control channel | ① 4~20mA: support 1~32 channels ② RS485: support 1-255 points |
Signal output | 4~20mA(optional) |
Alarm record | Alarm location display, alarm event recording, time, concentration |
Alarm value setting | A1, A2; interval alarm |
Alarm function | LED and buzzer sound |
Alarm output | 2 way common relay output, 8 programmable relay outputs |
Contact capacity | 220VAC,1A |
Communication Interface | RS-485 MODBUS; three RS-485 interface and one ethernet port |
Working temp | -20~55℃ |
Working humidity | 0~95% Relative humidity (no condensation) |
Environmental pressure | 86~106kPa |
Display | 7" or 9" touch TFT-LCD color screen,800x480 LCD |
Accuracy | ≤±1% |
Shell material | SPCC(SS304 or SS3i6 is optional) |
Dimensions | 300mm×400mm×100mm |
Weight | 6.5Kg |
Alarm method | Sound alarm 95 dB@30cm Red LED concentration indicator RTU-433 short distance wireless GPRS |
Buttons | Touch operation, with three-button operation of silencer, lock screen and flip screen |
Direct reading | Measured value, ambient temperature, humidity |
Data record | Automatic storage, can continuously store 300,000 sets of data with date and time, optional TF memory card, can store more than 10 million sets of data |
Data download | USB |
Data transfer | RTU-433 or GPRS(optional) |
Data print | Micro data printer serial port printing |
Calibration | 4mA, 12mA, 20mA three grade current calibration |
Protection | IP54 |
Operating mode | User mode, administrator mode |
Executive standard | GB 16808-2008 |
Main feature
1. 2 way common relay output (fault alarm, first level, second level alarm), 8 way programmable relay output;
2. Provide RS232 or RS485 communication interface with PLC or computer and Ethernet interface;
3. through the touch screen operating system menu, the main display screen displays the measured gas concentration value, alarm information, fault information, shielding information, storage information, installation location and other information;
4. The alarm record and data record in the TF memory card (optional) can be exported via USB;
5. Through the touch screen for alarm parameter setting, mask setting, system time setting, communication parameter setting, the current signal can be calibrated, and the alarm sound can be silenced.
6. Configurable backup power supply (optional), the main power and backup power automatically switch after the backup power work status icon is displayed visually in the menu bar;
7. The alarm channel number, alarm status and alarm time can be directly queried through the menu;
8. short-distance RTU wireless transmission mode or GPRS wireless transmission method with unlimited distance can transmit real-time detection data and alarm status to the security center through the built-in wireless module (optional);
Main function
Alarm function
The controller will give an audible and visual alarm when the following conditions occur:
1. When the measured gas concentration exceeds the set level 1 (A1 low report) alarm value or the second level (A2 high report) alarm value, the buzzer will emit continuous beep, the concentration alarm indicator will be on, and the common relay will draw. Combined
2. When the controller is connected to the gas detector circuit, such as: no signal output, transmission line drop, transmission line short circuit, gas detector signal output is out of the measurement range, the buzzer will emit continuous beep, and the fault alarm The indicator light is on and the public relay is connected;
3. When the main power is cut off, the buzzer will emit a short beep when the controller is powered by the backup power. When the backup voltage is insufficient, the buzzer will sound continuously.
Self-test function
When the power is turned on, the controller automatically checks the function of the indicator light and buzzer on the panel. The instrument self-test menu also performs a function self-test on the status indicator, buzzer and relay.
Data logging function
The historical data record and the real-time curve can be directly queried through the menu, and the data save interval can be customized. When the gas concentration of a channel exceeds the set alarm value, the alarm channel number, alarm concentration value and alarm time are automatically recorded.
Parameter setting function
The operating parameters of the controller can be viewed and modified at any time, including current date/time, measurement range, resolution, alarm values at all levels, channel shielding, installation location, and more.
Main and backup automatic switching function
When the main power of the controller is powered off, it can automatically switch to the standby power supply; when the main power is restored, it can automatically switch to the main power supply; the working status of the main and standby power supplies are indicated by indicators. When the main power supply is working, the backup power supply can be charged at the same time, and the standby power is automatically turned into a floating state after the backup power is full.
Alarm output control function
The controller has 2 common alarm output relays and 8 programmable alarm output relays. Control equipment for fire fighting equipment, ventilation equipment, alarm equipment, or other purposes. .
Current calibration function
The controller can calibrate the input 4mA, 12mA, 20mA current signal to ensure timely synchronization of the signal.
Communication function
The controller has three RS-485 interfaces and one Ethernet port, which can easily transfer data to other control devices, computers, and so on. The default address of the controller is: 5, and the baud rate is 9600.
Other functions
The total number of alarm channels is displayed, 4 to 20 mA current signal output, etc.
FIX-2100 gas alarm controller can be applied to the control and communication of standard 4~20mA current signal and bus system RS485 signal. The controller system adopts advanced high-precision single-chip processing technology. The whole machine has stable working condition, high measurement precision and strong versatility.
The FIX2100 gas alarm controller is connected to the gas detector to continuously monitor the dangerous gas in the environment, and displays the concentration of the measured gas according to the received input signal, and can communicate with the host computer through the RS-485 digital signal. Alarm records can be queried, stored, and controlled by relay outputs to control external devices such as exhaust systems or other external devices.